MMI 810.1 Mod 43 240v Control Box
Technical Data
Supply Voltage | 220 / 240 V (-15... +10%) 50 Hz (50 - 60 Hz) |
---|---|
AC frequency variations | result in proportional timing deviations |
Fuse Rating | max. 10 A rapid, 6 A slow |
Power Consumption | 10 VA |
Max. Current per Output | |
term. 3 | 2A, cos ϕ 0.2 |
term. 4, B | 2A, cos ϕ 0.4 |
term. 5, 6, C | 1A, cos ϕ 0.4 |
Total load | 5A, cos ϕ 0.4 |
Amplifier sensitivity | 1 µA |
Min. current from UV tube or ionisation probe | 5 µA |
Flame detector cable | max. 20 m cable length |
Waiting time for malfunction remedy | None |
Flame Detector | |
Ionisation Probe | |
Infrared Flicker Detector | IRD 1020 |
Weight incl. Base | 350g |
Mounting Position | Any |
Insulation Standard | IP 44 |
Admissible ambient temperature for controller and flame detector | -20° C… +60° C |
Classified acc. to EN 298 | BTLLXN |
MMI 810.1 Mod 43 240v Control Box
Gas Burner Automatic Safety Control
For 2 stage force draught and combi oil/gas burners
- Possible flame detectors:
- Ionization probe
- Infrared flicker detector
The gas burner automatic safety control MMI controls and monitors blown gas- and combined burners of any nominal thermal load (tested and certified according to EN 298).
The automatic safety controls MMI 810.1 models 13, 33 and 35 can also be utilized for burners on fixed hot air heaters (Direct air heaters according to DIN 4794).
Various types and model designations differentiate the automatic safety controls with respect to the programme times, as well as with regard to differing national standards.
MMI 810.1 Mod 43 Art. Nr. 0622520
MMI 810.1 Mod 43 | Program Timing Seconds. | |
---|---|---|
Waiting time at start ca. | tw | 9 |
Max. reaction time for air proving switch | tlw | 6 |
Pre-purge time | tv1 | 40 |
Pre-ignition time | tvz | 3 |
T. ignition time | tz | 6 |
Safety time | ts | 3 |
Time delay term.6/term.C | tv2 | 10 |
Datasheets |
---|