IRD1010 16502 Photocell End View C/W 1.8m Lead & Holder
Technical infomation
Supply Voltage | 220 / 240 V (-15... +10%) 50 Hz (50 - 60 Hz) |
---|---|
Nominal Current Input | approx. 4 mA |
Power Consumption | 1 VA |
Ambient Temperature | -20°C to +60°C |
Insulation Standard | IP 41 |
Mounting Attitude | Any |
Weight | 40g |
Flame viewing attitude | side-on or end-on according to type |
Spectral response | 800 - 1100 nm |
(with daylight filter) | maximum 950 nm |
Frequency range | 15 Hz.... 250 Hz (-12 dB) |
Sensitivity adjustment range | approx. 1 : 20 (26 dB) |
Switch-on delay (after connecting operating voltage) | < 3.5 sec. |
Response time | < 0.1 sec. |
Cut-out time | < 1 sec. |
IRD1010 16502 Photocell End View C/W 1.8m Lead & Holder
Infra-Red Flicker Detector
Flame monitoring device for yellow or blue burning oil flames
- Kit Contents
- Satronic IRD 1010 Flicker Detector Photocell end on
- 1.8m Lead to suit
- Holder to suit IRD 1010 Photocell
The IRD 1010 is employed to monitor the flame of an oil burner. This flame monitoring device should be connected to a Satronic oil burner control box. Monitoring is based on the infra-red flicker principle, in other words, the flickering infra-red light of the flame is detected. The steady radiation from, for example, the glowing refractory layer on the inside of the boiler, has no effect on the detector.
The IRD 1010 replaces the models IRD 910, 911 and 911 vi. If exchanging the units, care must be taken to connect them correctly.
Datasheets |
---|